RO membrane(equivalent to filmtec LP4040)

RO membrane(equivalent to filmtec LP4040)
Product Detailed
BW low energy ro membrane; size:4040; area:80feet; applicable to the water <2000ppm salt; equivalent to filmtec LP4040.

BDX4040B-ULP low energy ro membrane is used for the desalination of low salinity water and other similar water and it has high desalination rate and long time stable performance under high flow and low operating pressure (fall 20-40% compared with common low pressure membrane).BDX4040B-ULP low pressure ro membrane is applicable to the water which contains less than 2000ppm salt. It is used to produce pure water or ultra pure water in electronics, power, petrochemical, food, beverage and pharmacy.

 

 

Model

BDX4040B-ULP

Capability

Materials

PA(polyamide)

Average Salt Rejection%

99.5(99.0)

Permeate Flow gpd(m3/d)

2200(8.4)

Error

±15%

Active Membrane Area ft2(m2)

80(7.0)

 

Testing Conditions

 

Standard Solution

1500 ppm NaCl

Operating Pressure psi(Mpa)

 150(1.05)

Recovery Rate of Single Membrane Element

15%

Temperature deg C

25

PH Value of Solution

6.5-8.5

Test Time

Run for 30 minutes

 

 

 

 

Limiting Conditions

 

 

 

 

 

Max. Feedwater Temperature deg C

45

Max. Operating Pressure psi(MPa)

 600(4.12)

Max. Feedwater Flow gpm(m3/h)

16(3.6)

Max. SDI of Feedwater

5

Max. NTU of Feedwater

1

Concentration of Free Chlorineppm

< 0.1

PH Value Range of Feedwater as Continuous Operation

2-11

PH Value Range of Feedwater as Chemical Cleaning

1-11

Max. Pressure Difference of Single Membrane Element psi(MPa)

13(0.09)

The minimal proportion of single membrane element's conc. press to perm. flow

5 : 1